ADP100 Premix Analyser
Air/gas ratio analyser for industrial burners
Stabilise the flame of your burners and optimise the energy efficiency of your furnaces.
The ADP100 continuously measures and regulates the air/gas ratio sent to industrial gas burners, to stabilise the flame, optimise furnace temperature and reduce fuel consumption. Designed for the glass, steel and ceramics industries, it combines a 5-second response, high accuracy and maintenance-free operation.
5-second response
Near-instantaneous adjustment of the air/gas ratio
Zirconia cell
Residual oxygen measurement by catalytic combustion
High accuracy
± 0.1% over the 0-5% O2 range
Maintenance-free
Rugged design, little upkeep
Compact and portable
19 kg, 500 x 260 x 450 mm
Quick start-up
Simple to use, immediate commissioning
The premixed air/gas mixture sent to the burner is analysed in a chamber where catalytic combustion takes place, followed by measurement of the residual oxygen in the combustion products by a zirconium oxide cell. This measurement is linearised and then converted into a percentage of O2 and fuel, with a 4-20 mA output that can be used directly by the furnace control system.
Measurement by zirconium oxide cell
Catalytic combustion of the mixture, then measurement of residual oxygen
Linear 4-20 mA output
Directly usable by the furnace's existing control system
5-second response
Near-instantaneous adjustment of the air/gas ratio
Configurable measuring range
From 10% excess fuel to 21% excess oxygen
Compact, maintenance-free design
Portable device, available in 230 V or 110 V
| Measurement principle | Residual oxygen by zirconium oxide cell, after catalytic combustion of a fixed mixture |
|---|---|
| Measuring range | Configurable from 10% excess fuel to 21% excess oxygen |
| Accuracy (excess oxygen) | ± 0.1% over 0-5% O2; ± 2% of the measured value over 5-21% O2 |
| Accuracy (excess fuel) | ± 0.25% over 0-5%; ± 5% of the measured value over 5-10% |
| Repeatability | ± 0.2% of the measured value |
| Display | % O2 – % excess fuel |
| Analogue output | Linear 4-20 mA (e.g. 4 mA = 10% fuel, 20 mA = 21% O2, 9.16 mA = stoichiometry) |
| Sample flow rate | 30 to 50 L/h |
| Sample pressure | 1 bar maximum |
| Electrical supply | 230 VAC 50 Hz or 110 VAC 50/60 Hz |
| Power consumption | 500 W |
| Dimensions (L x W x H) | 500 x 260 x 450 mm |
| Weight | 19 kg |
| Ambient temperature | 10 à 40 °C |
| Reference (230 V version) | ARCADP100+ |
| Reference (110 V version) | ARCADP100-B+ |
Applications
Glass industry
Steel Industry
Ceramics
Industrial furnaces
Thermal processes using gas burners
FAQ
Got a project? Our experts are ready to help.
Personalised advice, a fast quote and technical support to choose the solution that fits your needs.